Recording cycle: 1 sec to 12 hours
nput types: Thermocouple, resistance bulb, DC voltage, and DC current (Shunt resistors are
fitted in input terminals).
Note) Provide a shunt resistor (type
PHZP0101) separately.
Measuring range
Note) B, R, S, K, E, J, T : JIS C 1602, DIN IEC 584-1
N : NICOSIL-NISIL (IEC 584)
W : 5%Re-26%Re · W (Hoskins Mfg. Co. USA)
L : Fe-Cu · Ni (DIN 43710)
U : Cu-Cu · Ni (DIN 43710)
PN: Platinum
JPt100 : JIS C 1604-1989 (Old JIS Pt 100)
Pt100, Pt50 : JIS C 1604, DIN IEC 751
Selection of input types:
By key operation on the front panel. Note
that the same input type (thermocouple,
resistance bulb, voltage) should be set ev-
ery 2 channels. Refer to “Setting method
of input types” for details.
Burn-out function:
Equipped in thermocouple and resistance
bulb inputs as standard, and overswings
the recording to 100% side.
Thermocouple burn-out current:
approx. 0.2 µA
Input filter function:
Settable for each channel (primary delay
fi lter) Time constants are settable in the
range from 0 to 900 sec.
Scaling function: Possible by DC voltage (current) input
Scaling range: -32767 to 32767
Decimal position: settable at any point Unit symbol: settable up to 7 digits and
125+12 types
Subtraction function:
Subtraction between each channel is al-
lowed.
Totalizing function:
The measured value of each channel can
be totalized. The base time can be select-
ed from Day, Hour, Minute, and Second.
F value calculation function:
F value (extinction value of bacteria by
sterilization by heating) can be calculated
from the measured temperature by each
channel.
Square rooter function:
Square rooter can be performed against
the input value per each channel.
Logarithmic calculation function:
The measured value of each channel can
be displayed in exponent form.
Mathematics function:
The math function as shown below is
available.
1) Formula
It can be set 1 main formula and 3 tem-
porary one.
Addition, Subtraction, Multiplication,
Division Absolute value, X to the power
of Y, Logarithm, Natural logarithm, Ex-
ponential function, Humidity, Average,
Maximum, Minimum.
2) Input signal
DI (DI1 to DI10), Totalize (ch1 to ch30),
Analog input (ch1 to ch30), Constant
(No.1 to No.20), Communication input
(No.1 to No.12)
Indication system
Indicator: 5.7” TFT color LCD (320 × 240 dots)
with backlight, no contrast adjustment
Note) The LCD may have some pixels that do not stay on or off.
Due to the characteristics of liquid crystal, the
brightness may not be uniform, which is not a
failure.
Color of indication:
14 colors
Applicable language:
English, French, German, Italian (switchable)
Life of backlight: 50,000 hours (20°C)
(the complete indicator unit should be replaced when replacing backlight).
Trend display: Direction: vertical and horizontal
Number of channels: 10 channels or 4
channels for the group on one screen (In-
put: 18 points at the maximum).
Display refreshment cycles:
select from 1 second to 12 hours
No numerical value display. Scale display/
no-display can be selected.
Bar graph display:
Direction: vertical
Number. of channels: 10 channels or 4
channels for the group on one screen (In-
put:18 points at the maximum).
Display refreshment cycles: 1 second.
Analog meter display:
Display for up to 4 inputs per group (input
from 1 to 4). Display in bar graphs or in
analog meters can be selected.
Display refresh cycle: 1 second
Digital display: Number of channels: 10 channels or 4
channels for the group on one screen
(Input:18 points at the maximum).
Display refreshment cycles: 1 second.
Totalizing data display:
Number of channels: 10 channels or 4
channels for the group on one screen (In-
put: 18 points at the maximum)
Display refresh cycle: 1 second.
Event summary display:
Alarm summary and message summary
can be displayed. The message occur-
rence information and message display
can be switched.
Ethernet log display:
E-mail sending, FTP server log in/off and
MODBUS TCP/IP communication start/
stop can be displayed.
Parameter display/set:
Already-set Data Display and Set Change
Display screen
TAG indication: Number. of characters to be displayed:
Up to 8 characters (note 1) at 10 chan-
nels on one screen or up to 16 (= 8
× 2) characters at 4 channels on one
screen.
Note 1: On some screen, it can be
displayed only 7 characters.
Characters to be displayed:
Alphanumerical characters
Tag, unit and channel number display:
It depends on the screen. See below
table.
Historical trend display:
The past data can be displayed from the
Compact Flash or internal memory. The
past data fi le can be read and displayed
with scroll display function or jump the
cursor to the position which you entered
date and time. Scale display/no-display
can be selected.
Number of screen groups:
Four groups (Up to 10 channels per 1
group can be registered.)
Keyboard
No. of Keys: 8
Function: Use to select various screens and set
various parameters.
Recording function External memory media:Compact Flash card
(Format as FAT32, FAT16 or FAT, or re-
corder can’t read and write.) Recording capacity:
2 GB maximum (compact fl ash). Limiting
the recording file to 64 MB is recom-
mended (for 112 hours if display refresh
cycle is 1 second. See Table 1 (p. 7).)
(When the size of the recording file
comes to be 256 MB or more, a new fi le
is created automatically and recording is
maintained.)
* Please change the compact fl ash every
six month to prevent the data losing.
Recording method:
Turning ON the REC key allows measured
data to be written at fi xed cycles.
Recorded as a new file whenever the
recording starts
Data save cycles:
Linked to the display refreshment cycles
on the “Trend display” screen. However,
they are automatically set to about 1 min-
ute if the refreshment cycles are set to
less than 1 minute.
Trend data: Average, instance or min. and max. mea-
sured values out of measured data that
are sampled at the measuring cycles are
saved.
Event data: Saves alarm data, message data and
power ON data when the power turns off
and on during recording.
Totalizing value data:
Totalizing value data at designated timing
is recorded per channel.
Totalized value data at designated total-
ized value recording cycle or the sum
total is recorded in the totalizing fi le.
You can choose which type you want to
record.
For each cahnnel. it can be select as total-
izing action from Analog input totalization,
Digital input count or period of Digital
input ON, and it can be select as totalizing
period type from Dairy, Weekly, Monthly,
Annual, Periodic, Dairy (time set) or Exter-
nal input signal.
Even if a power failure occues during total-
ization and then the power is restored,the
totalization restarts from the value before
power failure.
Storage capacity :
Approximately 3 years when the display
refresh cycle is 30 seconds (in the case of
9-channel recording in ASCII data format,
and 512 MB Compact Flash is used).
Refer to Table 1.
Residual capacity of memory:
Indicates the memory which has already
used on the screen. When all the mem-
ory is used up, you can stop recording or
delete the oldest recording fi le to save
the newest data.
Compact fl ash card form: PHZP1301-512
(CF card) (If a card other than the above is used, no
operation assurance is ensured.
Meanwhile, as for other CF cards for
which operation check will have been
completed, the results will be posted on
our company's homepage sequentially.
Please refer to this website.)
Recommended PC card adaptor:
SanDisk Corp. SDAD-38
Data format: Either of ASCII or binary format can be
selected. (Switching cannot be made
while the recording is in progress. In the
case of ASCII format, the data can be directly read on Excel, etc.)
Note: The data recorded in binary format
cannot be read directly.
Approximately 166 bytes per 1 sampling
(for 9-channel input in ASCII format) or ap-
proximately 40 bytes (for 9-channel input
in binary format)
Alarm function
No. of settings: Up to 4 alarms for each channel are set-
table.
Type of alarm: High/Low limits
Indication: Status (alarm types) is displayed on digital display unit when an alarm occurs.
History display on alarm summary (Alarm start/cancel time and alarm types)
Hysteresis: Set within the recording range of 0 to 100% (it is effective only in case of high/low limit alarm)
Relay output: Number of points; 10 (option: Cannot be selected if the number of input points is 18.)
Transistor output (Open collector):
Number of points; 18 (option)
Alarm latch function:
Keeps alarm indication and alarm output
turning on after alarm reset.
ON/OFF operation is performed according
to key setting.
Power supply
Rated power voltage:
100 to 240V AC
Range of operating voltage:
90 to 264V AC
Supply frequency:
50/60Hz (both employable)
Power consumption
100V AC
About 36VA
240V AC
About 47VA
Structure Mounting method:
Panel-mounted (vertical panel)
Thickness of panel:
2 to 26 mm Materials: PC-ABS for case and bezel Color: Black External dimensions: Panel-mounted: 160 (W) × 144 (H) × 185 (D) mm Mass: About 1.5 kg (no option) External terminal board:
Screw terminals (M3 thread)
RJ45: Ethernet terminal (option)
Normal operating condition
Power voltage: 90 to 264V AC
Supply frequency:
50/60 Hz ±2% (both employable)
Ambient temperature: Panel-mounted
0 to 50°C (without Ethernet option*1)
0 to 40°C (with Ethernet option*2)
Ambient humidity:
20 to 80%RH Vibration: 10 to 60Hz 0.2m/s2 or less Shock: None Magnetic field: 400 A/m or less Signal source resistance:
Thermocouple input …. 1k or less
Resistance bulb input … 10 /wire or less
(resistance of each wire of 3-wire system
should be balanced).
Voltage input … 0.1% or less of input
resistance Mounting posture:
Forward tilt 0°, backward tilt within 30°,
horizontal 0°
Warm-up time: One hour or more after power ON
Environmental protection:
IEC IP50 (Front)/20 (Terminal)
Installation category:
II
Pollution degree: 2
Operating altitude:
2000m max.
*1: In case of the 12th digit of ordering code is ”Y” or ”R”.
*2: In case of the 12th digit of ordering code is ”E” or ”W”.
Safety and EMC standard
Safety standard: Based on IEC61010-1
EMC standard: Based on EN61326
Transportation/storage conditions
Temperature: −10 to +60°C
Humidity: 5 to 90%RH, no condensation
Vibration: 10 to 60Hz, 2.45m/s2
or lower
Shock: 294m/s2
or lower (packed state) Reference standard Accuracy/resolution:
Measuring conditions (23±2°C, 65±10% RH, power voltage, frequency fl uctuation within ±1%, no external noise, warm-up time of 1 hour or more, vertical mounting, standard values of signal source resistance and wiring resistance... within 1% )
Note 1) Digital indication accuracy is a percentage (%) of the value in the measuring range on page 1.
Note 2) No error of reference contact compensation of thermocouple is included. Error of reference contact compensation:
K, E, J, T, N, L, U, PN: ±0.5°C
R, S, B, W: ±1.0°C
(when measured at 0°C or more)
Max. input voltage:
Thermocouple, resistance bulb, DC volt-
age: ±10V DC (continuous)
nput resistance: Thermocouple, DC voltage:
About 1M
Others Clock: With calendar function (Christian era) Accuracy: ±100ppm or less (monthly error: about 4 minutes)
However, time error at ambient temperature 23±2°C and power ON/OFF is not
included. Memory backup: Parameters are saved to the internal nonvolatile fl ash memory.
The clock and totalized data are backed up with built-in lithium battery.
Insulation resistance:
100M or more (when measured between each terminal and ground by using a 500V DC megger) Withstand voltage:
Power terminal – ground: 2000V AC, 1 min
Input terminal – ground: 500V AC, 1 min
Alarm terminal – ground: 2000V AC, 1 min
Alarm terminal – alarm terminal:
750V AC, 1 min
Communication terminal – ground:
500V AC, 1 min
Alarm terminal (open-collector) – ground:
500V AC, 1 min